Hackers Set Freezer Controls to 100°C, Then Lock Technicians Out of the System

Blog WriterCybersecurity News - Original News Source is cybersecuritynews.com


Hackers changed a freezer chamber’s temperature setting to 100°C at Salamerija Alpija, a meat processing plant in Tolmin, Slovenia. When a service technician tried to sign in to the cooling control system, his access was blocked.

Instead of the controls, his screen showed a photo of Italian minister Matteo Salvini with a caption that translates as “Thank Uncle Matteo,” cooperative director Nikola Šavle told Slovenian news outlet 24ur.

The freezer did not reach 100°C. That was the setting entered in the control system, not the temperature measured inside the chamber. Šavle said staff caught the change before temperatures rose and no meat products spoiled.

The Tolmin Agricultural Cooperative estimated that about €250,000 worth of goods could have been lost. That figure represents stock at risk, not a confirmed financial loss.

Hackers Changed Freezer Temperature

The first sign of trouble came around noon, when an employee noticed the 100°C setting during a check at the salami plant. Staff knew about recent attacks on supermarket refrigeration systems across Europe, so they checked cooling equipment at other cooperative sites.

They found another problem at the slaughterhouse and discovered that a refrigerator at one of their stores had been set to 20°C instead of its usual 2–3°C.

The cooperative managed temperatures across its cold rooms and chambers through an internet-connected system. Staff disconnected the cooling equipment from the network and set the temperatures manually.

The technician’s blocked login meant the team could not rely on the usual computer interface to restore the settings. The public report does not explain how his login was blocked or whether anyone had changed his account settings.

The cooperative’s alarm was designed to warn staff about an unexpected drop in temperature. This time, Šavle said the target appeared to have been changed in the digital system, and staff received no warning.

The distinction matters: an alarm that watches the temperature inside a room may not tell staff that someone has changed the target the equipment follows.

The cooperative added in-person checks, with staff due to review settings every few hours. Šavle questioned what would have happened on a weekend, when production sites are not staffed.

The cooperative said it planned to report the incident to Slovenia’s national cyber response center, SI-CERT. The Slovenian Press Agency also reported the attack.

The Tolmin incident shares a visible feature with attacks on European supermarkets: someone changed cooling settings without permission. That does not establish that the same people were responsible or that they used the same equipment or method.

The Salvini image also does not establish who was behind the attack or why they targeted the plant. Separately, the U.S. Cybersecurity and Infrastructure Security Agency published a November 24 advisory on Danfoss commercial refrigeration controllers.

The Tolmin report did not identify the controller maker or model, explain how the attackers got in, or name a suspect. There is no public evidence in that report linking the Danfoss flaw to the incident.

Refrigeration controllers are part of operational technology, the equipment and software that monitor or control physical processes. For food producers, a useful starting point is an inventory of operational technology assets.

It should show which controller serves each room, who can change its settings, and how outside service teams connect. CISA’s guidance for operational technology operators recommends removing direct access from the public internet, separating control equipment from business networks, and using strong sign-in controls where remote access is necessary.

It also recommends practicing manual operation so staff can keep equipment running safely if they lose remote access. Operators can use an independent sensor to warn staff when a room leaves its approved temperature range, regardless of what the controller is set to. A separate alert for an unexpected change to the target can flag trouble before the room warms.

Both alerts need to reach someone who can act outside normal working hours. In Tolmin, a routine walk-through caught what the alarm did not.

The test for another cold storage operator is whether the same change would wake someone on a Sunday, and whether that person could restore safe settings without logging in remotely.

Give your SOC the alert context on the latest threats to stop incidents quickly -> Integrate Threat Intel from 16K SOCs

The post Hackers Set Freezer Controls to 100°C, Then Lock Technicians Out of the System appeared first on Cyber Security News.